Jump to content

IEC standards for PV performance testing

From Appropedia

Notes to Reader

[edit | edit source]

Put any information relevant to reviewing, contributing, or using this review page.

IEC 61215: part 1-—Terrestrial PV Modules—Design Qualification and Type Approval (an adoption with Canadian deviations)

[edit | edit source]
  • presents requirements for design qualification for long-term operation in open-air climates
  • useful module's life qualification will depend on their design, environment and condition under which it is operated
  • not applicable for flexible modules installed in awning or tenting
  • Objective:
    • Determine the electrical characteristics of the module
    • Capability of withstanding prolonged exposure outdoors as far as possible within reasonable constraints of cost and time
  • Testing
    • test lab should use lab simulator control module to be able to detect drifts in their measurements
    • modules should be divided into groups and subjected to the qualification test sequences
    • junction box shall pass IEC 61214-2:201 x MQT 14.2, which cites IEC 62790 "Test of Cord Anchorage"
    • connectors shall pass IEC 62852
    • if the sample size (in modules) <10: all modules shall pass; no failure is allowed
    • if the sample size (in modules) >= 10: A single failure is allowed. all other modules shall pass
  • List of Apparatus⁣⁣ Required:
    • Natural sunlight
    • Solar simulator class BBA or better
    • A PV Reference device:
      • IEC 60904-2 reccomnended device
      • a reference module of the same size with the same technology to match spectral responsivity (if BBA simulator is used)
      • class AAA solar simulator (alternative)
      • A class of CCC solar simulator or better, in accordance with IEC 60904-9
    • IEC 60904-1 recommended I-V curve tracer
    • DC voltage source with current limitation, capable of applying 500 V or 1000V, plus twice the maximum system voltage of the module.
    • Instrument to measure insulation resistance
    • A suitable mount support
    • Equipment necessary to change the irradiance to 200W/m² without affecting the relative spectral irradiance distribution and the spatial uniformity.
    • Temperature sensor for monitoring the temp. of the test specimen and the reference device to an accuracy of ±1°C and repeatability of ±0.5°C
    • An open rack to minimize heat conduction from the modules to interfere as little as possible with the free radiation of heat from their front and back surfaces.
    • A solar irradiation monitor accurate to ±5%
    • Suitable resistive loads (variable)
    • Ameter
    • Opaque cover for test cells, shadowing according to the technology-specific parts of IEC 61215
    • An IR camera to measure and record the module temp
    • Equipment to record irradiance levels, integrated irradiance and ambient temp.
    • A temp-controlled test chamber with a window or fixture for a UV light source and the module under test to maintain (60±5)°C
    • UV light source ( 280nm to 400nm) with an irradiance uniformity of ±15%
    • Intruments to measure irradiance of UV light
    • A climatic chamber with automative temperature control with means for circulating the air inside and means to minimize condensation on the module during the test, capable of subjecting one or more modules to the thermal cycle.
    • Mounting system for mounting the modules in the chamber, so as to follow free circulation of the surrounding air.
    • A climatic chamber with automatic temp and humidity control, capable of subjecting one or more modules to the humidity-freeze cycle
    • Device for monitoring, throughout the test, the continuity of the internal circuit of each module.
    • Instrument for applying a force of 40N
    • A shallow trough or tank of sufficient size
    • Spray equipment
    • A rigid test base that allows the modules to be mounted either front side up or down.
    • Instruments to apply appropriate weights or pressure mechanisms must be provided to ensure that the load can be applied gradually and evenly.
    • moulds of suitable material for casting spherical ice balls (min diameter of 25mm)
    • A freezer controlled at (-10±5)°C
    • a storage container for sorting the ice balls at (-4±2)°C
    • A launcher capable of propelling an ice ball.
    • mounting support according to manufacturer's instruction
    • A balance to measure the mass of ice ball to an accuracy of (±2)%
    • An instrument to measure the velocity of ice ball to an accuracy of (±2)%
    • Instrument for heating the module to a temp of (90±5)°C
    • Current source for applying a current equal to 1.25 times the STC short-circuit current

Summary of test levels

[edit | edit source]
MQT Title Purpose/Failure Mode Test Procedure Apparatus
1 Visual inspection Visual defects detection carefully inspect each module under an illumination of not less than 1000 lux for conditions [see list of major visual defects]
2 Maximum power determination To determine max. Power of the module after stabilization as well as before and after various environmental stress test. determine I-V characteristics of the module at specific set of irradiance and temp condition. Recommended range is a cell temp between 25°C and 50°C and an irradiance between 700 W/m2 and 100 W/m2. Every effort should be made to ensure that peak power measurements are made under similar operating conditions.
  • radiant source (natural sunlight or a solar simulator class BBA or better)
  • a PV reference device in accordance with IEC 60904-2. If a class BBA simulator or better is used, the reference device shall be a reference module of the same size with the same technology to match spectral responsivity. Upon unavailability:
    • a class AAA simulator can be used, or
    • the spectral responsibility of the module according to IEC 60904-8 and the spectral distribution of the solar simulator need to be measured, and the module data corrected according to IEC 60904-7
  • a suitable mount for supporting the test specimen and the ref device in a plane normal to the radiant beam
  • apparatus for measuring I-V curve in accordance with IEC 60904-1
3 Insulation test To determine whether or not the module is sufficiently well insulated between live parts and the accessible parts. Test Condition: at ambient temperature of the surrounding atmosphere and in a relative humidity < 75%

Procedure:

  1. Connect the sorted o/p terminal of the module to the positive terminal of a DC insulation tester.
  2. Connect the exposed metal part of the module to the -ve terminal of the test.
  3. Increase the voltage applied by the tester at a rate not exceeding 500V/s to a max qual of (100v + 2* max system voltage). If the max system voltage does not exceed 50v, the applied voltage will be 500v. Maintain the voltage at this level for 1 min.
  4. Reduce the applied voltage to 0v and short-circuit the terminals of the test equipment to discharge the voltage build-up in the module.
  5. remove short-circuit
  6. Increase the voltage at a rate not exceeding 500 V/s to 500 V or the maximum system voltage (whichever is greater). Maintain for 2 min at this level and determine insulation resistance.

**if the module area < 0.1 m2 , the insulation resistance should not less than 400 MΩ

**if the module area > 0.1 m2, the measured insulation resistance * module area should not be less than 40MΩ. m2.

  • DC voltage source with current limitation, capable of applying 500 V or 1000V, plus twice the maximum system voltage of the module.
  • instrument to measure insulation resistance
4 Measurement of temperature coefficients Determine the temp coefficient of current (α), voltage (β) and peak power (δ). the coefficients so determines are valid at the irradiance at which the measurements were made. See IEC 60904-10 for evaluation of module temp. Coefficients at different irradiance levels.
5 Measurement of nominal module operating temperature (NMOT) to gather actual measured mosule temperature data under a range of environmental conditions including standard reference environment (SRE):

- Titl angle: (37±5)° -Total irradiance: 800 W/m² -Ambient temp: 20° C -Wind speed: 1m/s -Electric load: resistive load sized such that tehmodule will operate near its MPP at STC or an electronic MPPT

for calculating NMOT should be acquired using the test method in IEC 61853-2.
6 Performance at STC to determine how the electrical performance of the module varies with load at STC 1000 W/m2, 25°C cell temp.
  • radiant source (natural sunlight or a solar simulator class BBA or better)
  • a PV reference device in accordance with IEC 60904-2. If a class BBA simulator or better is used, the reference device shall be a reference module of the same size with the same technology to match spectral responsivity. Upon unavailability:
    • a class AAA simulator can be used, or
    • the spectral responsibility of the module according to IEC 609-04-8 and the spectral distribution of the solar simulator need to be measured and the module data corrected according to IEC 60904-7
  • a suitable mount for supporting the test specimen and the ref device in a plane normal to the radiant beam
  • a means for monitoring the temp of the test specimen and the reference device to an accuracy of ±1°C and repeatability of ±0.5°C
  • apparatus for measuring I-V curve in accordance with IEC 60904-1
7 Performance at low irradiance To determine how the electrical performance of the module varies with load at 25°C and an irradiance of 200 W/m2.
  • radiant source (natural sunlight or a solar simulator class BBA or better)
  • equipment necessary to change the irradiance to 200W/m² without affecting the relative spectral irradiance distribution and the spatial uniformity.
  • a PV reference device in accordance with IEC 60904-2. If a class BBA simulator or better is used, the reference device shall be a reference module of the same size with the same technology to match spectral responsivity. Upon unavailability:
    • a class AAA simulator can be used, or
    • the spectral responsibility of the module according to IEC 609-04-8 and the spectral distribution of the solar simulator need to be measured and the module data corrected according to IEC 60904-7
  • a suitable mount for supporting the test specimen and the ref device in a plane normal to the radiant beam
  • a means for monitoring the temp of the test specimen and the reference device to an accuracy of ±1°C and repeatability of ±0.5°C
  • apparatus for measuring I-V curve in accordance with IEC 60904-1
8 Outdoor exposure test To amke a priliminary assessment ofteh ability of the module to withstand exposure to outdoor conditions and to reveal any synergistic degradation effects which may not be detected by laboratory tests.
  • an open rack to support the test module and solar irradiation monitor in the specified manner. the rack should be designed to minimize heat conduction from the modules to interfere as little as possible with the free radiation of heat from their front and back surfaces.
  • a solar irradiation monitor accurate to ±5%, mounted in the plane of the modules within 0.3 m of the test array
  • means to mount the modules
  • a resistive load sized such that the module will operate near its MPP or an electronic MPPT
9 Hot-spot endurance test Hot spots

Shunts in cells or at scribe lines Inadequate by-pass diode protection

  • radiant source: natural light or a class BBB (or better) steady-state solar simulator with an irradiance of 800 W/m² to 1100 W/m²
  • I-V curve tracer
  • ameter
  • opaque cover for test cells, shadowing according to the technology-specific parts of IEC 61215
  • An IR camera to measure and record the module temp
  • equipment to record irradiance levels, integrated irradiance and ambient temp.
10 UV preconditioning Delamination

Encapsulant loss of adhesion & elasticity Encapsulant & backsheet discoloration Ground fault due to backsheet degradation Degradation of Optics

  • A temp-controlled test chamber with a window or fixture for a UV light source and the module under test. it should be capable of maintaining the module's temperature at (60±5)°C
  • A means for monitoring module's temp to an accuracy of ±2°C and repeatability of ±0.5°C. the temp sensor should be attached to the front and back surfaces of the module near the middle without obstructing anuy of the UV light incident
  • instruments to measure the irradiance of UV light produced by the UV light source from 280 nm to 400nm.
  • A UV light source capable of producing UV radiation with an irradiance uniformity of ±15%.
  • for light sources with a negligible spectral content in the visible range the module should be short circuited. alternatively the module can be connected to a load sized such that the module will operate near the MPP. the latter is recommended for light sources emitting a significant portion of light in the visible spectrum where the module exhibits a power equal to or larger than 20% of its STC measures power.
11 Thermal cycling test to determine the ability of the module to withstand thermal mismatch, fatigue and other stresses caused by repeated changes of temperature.

Broken interconnect Broken cells Electrical bond failure Junction box adhesion Module open circuit – potential for arcing

  • a climatic chamber with automative temperature control with means for circulating the air inside and means to minimize condensation on the module during the test, capable of subjecting one or more modules to the thermal cycle.
  • Means for mounting the modules in the chamber, so as to follow free circulation of the surrounding air. the thermal conduction of the mount or support should be low, so that, for partial purposes, the modules are thermally isolated
12 Humidity-freeze test Delamination

Junction box adhesion Inadequate edge deletion*

to determine the ability of the module to withstand the effects of high temp and humidity followed by sub-zero temp.

  • a climatic chamber with automatic temp and humidity control, capable of subjecting one or more modules to the humidity-freeze cycle.
  • Means for mounting the modules in the chamber, so as to follow free circulation of the surrounding air. the thermal conduction of the mount or support should be low, so that, for partial purposes, the modules are thermally isolated
  • measurement instrumention having an accuracy of ±2°C and repeatability of ±0.5°C for measuring and recording the temp of the module
  • means for monitoring, throughout the test, the continuity of the internal circuit of each module.
13 Damp-Heat test Corrosion

Delamination Encapsulant loss of adhesion & elasticity Junction box adhesion Electrochemical corrosion of TCO* Inadequate edge deletion*

test temp: (85±2)°C

relative humidity: (85±5)% test duration: 1000 h

the test shall be carried out in accordance with 60068-2-78
14 Robustness of termination test to determine that the terminations, the attachment of the terminations, and the attachment of the cables to the body of the module will withstand stresses that are likely to be applied during normal assembly or handling operations. test should be performed 2h to 4h after completion of MQT 12.

the pull force should be applied at the center point of the box.

instrument for applying a force of 40n to the centre of the test object. prevent torque from being applied to the junction box.
15 Wet leakage current test to evaluate the insulation of the module under wet operating conditions and verify that moisture from rain, fog, dew or molten snow does not enter the active parts of the module circuitry, where it might cause corrosion, a ground fault or a safety hazard.
  • A shallow trough tank must be of sufficient size to accommodate the module with its frame, allowing it to be placed flat and in a horizontal position within the solution. It should contain enough water or wetting solution to adequately wet the surface of the module while meeting the following requirements:
    • resistivity: 3500ohm/cm or less
    • Solution temperature: (22±2)°C
  • Spray equipment
  • Dc voltage source with current limitation
  • Intrument to measure insulation resistance
16 Static mechanical load test Structural failures

Broken glass Broken interconnect ribbons Broken Cells Electrical bond failures

To determine the ability of module to withstand a minimum static load

  • A sturdy test base is required, allowing the modules to be mounted either with the front side facing up or down. This test base should enable the module to deflect freely during load application, following the manufacturer's recommended mounting method. An electrical continuity measurement device is also necessary. Additionally, appropriate weights or pressure mechanisms must be provided to ensure that the load can be applied gradually and evenly.
17 Hail test Broken glass

Broken cells Broken Optics

  • moulds of suitable material for casting spherical ice balls (min diameter of 25mm)
  • A freezer controlled at (-10±5)°C
  • a storage container for sorting the ice balls at (-4±2)°C
  • A launcher capable of propelling an ice ball.
  • mounting support according to manufactures instruction
  • A balance to measure the mass of ice ball to an accuracy of (±2)%
  • An instrument to measure the velocity of ice ball to an accuracy of (±2)%
18 Bypass diode thermal test Bypass diode failures

Overheating of diode causing degradation of encapsulant, backsheet or junction box

  • Instrument for heating the module to a temp of (90±5)°C
  • Temp sensor
  • voltage measurement instrument for measure junction voltage
  • current source for applying a current equal to 1.25 times the STC short-circuit current
  • I-V curve tracer
19 Stabilization - A class of CCC solar simulator or higher, in accordance with IEC 60904-9.

- An instrument to measure irradiation.

- A mounting structure that is co-planar with the reference device.

- Use the reference device to set the irradiance between 800 W/m² and 1000 W/m².

- A temperature sensor.

- A resistive load.

20 Cyclic (Dynamic) mechanical load test Broken glass

Broken interconnect ribbons Broken Cells Electrical bond failures

check IEC TS 62782
21 Potential induced degradation test (PID)
22 Bending test - for flexible modules only
Page data
Part of FAST
Keywords IEC, PV performance, test requirement, test procedure
SDG
Authors Riya Roy
License CC-BY-SA-4.0
Language English (en)
Translations Uzbek
Related 1 subpages, 3 pages link here
Views 90 page views (analytics)
Created April 28, 2025 by Riya Roy
Last edit May 1, 2025 by StandardWikitext bot
Project data
Type
Authors Riya Roy
Location London, ON
Status
Years
OKH Manifest Download
Cookies help us deliver our services. By using our services, you agree to our use of cookies.