== Introduction ==
== Introduction ==


[http://www.Eurekafloorcarpetoneeureka.com/ Eureka Floor Carpet One] (Figure 1) sells floor coverings and performs installments to homes and commercial businesses across Humboldt County, California. Carpet One experiences customer visits sporadically throughout the day, sometimes several hours or just a few minutes apart, so lights must remain on constantly during business hours. With the assistance of the [http://www.redwoodenergy.org/ Redwood Coast Energy Authority] (RCEA), Eureka Floor Carpet One replaced it's old lighting system with new energy efficient lighting. <ref name="A">[Mike Jurkovich. Personal Communication. October 20, 2009]</ref>  
[http://www.Eurekafloorcarpetoneeureka.com/ Eureka Floor Carpet One] (Figure 1) sells floor coverings and performs installments to homes and commercial businesses across Humboldt County, California. Eureka Floor Carpet One experiences customer visits sporadically throughout the day, sometimes several hours or just a few minutes apart, so lights must remain on constantly during business hours. With the assistance of the [http://www.redwoodenergy.org/ Redwood Coast Energy Authority] (RCEA), Eureka Floor Carpet One replaced it's old lighting system with new energy efficient lighting. <ref name="A">[Mike Jurkovich. Personal Communication. October 20, 2009]</ref>  


<br>
<br>
Before the lighting retrofits, Carpet One experimented with motion-sensing switches to save energy. Even though Carpet One was saving Kilowatt-hours, they reported replacing light bulbs more frequently. Before the installment of electronic ballasts during the lighting upgrade, Carpet One had magnetic ballasts. Each time an older magnetic ballasts stopped working, an electrician would have to be hired to fix it. By participating in the RCEA lighting upgrade, Carpet One could replace all of the ballasts at once, with the intention of saving time and money on maintenance.<ref name="A">[Mike Jurkovich. Personal Communication. October 20, 2009]</ref>
Before the lighting retrofits, Eureka Floor Carpet One experimented with motion-sensing switches to save energy. Even though Eureka Floor Carpet One was saving Kilowatt-hours, they reported replacing light bulbs more frequently. Before the installment of electronic ballasts during the lighting upgrade, Eureka Floor Carpet One had magnetic ballasts. Each time an older magnetic ballasts stopped working, an electrician would have to be hired to fix it. By participating in the RCEA lighting upgrade, Eureka Floor Carpet One could replace all of the ballasts at once, with the intention of saving time and money on maintenance.<ref name="A">[Mike Jurkovich. Personal Communication. October 20, 2009]</ref>


== Lighting Retrofits ==
== Lighting Retrofits ==
Line 13: Line 13:
[[Image:Carpet1.jpg|thumb|right|250px|'''Figure 2. Lighting Retrofits Performed on Eureka Floor Carpet One by the Redwood Coast Energy Authority''']]  
[[Image:Carpet1.jpg|thumb|right|250px|'''Figure 2. Lighting Retrofits Performed on Eureka Floor Carpet One by the Redwood Coast Energy Authority''']]  


Eureka Floor Carpet One's main purpose for performing the lighting retrofits (Figure 2.) was because of the cost benefit-analysis from a small business stand point. Carpet One was looking for a more energy efficient lighting system and a means to replace their older, magnetic ballast lighting system which had been less cost-effective. <ref name="A">[Mike Jurkovich. Personal Communication. October 20, 2009]</ref> Seventy-four retrofits were performed by the RCEA in April of 2006. A complete list of RCEA retrofits is located in the Summary of Completed Retrofits(Table 3.)
Eureka Floor Carpet One's main purpose for performing the lighting retrofits (Figure 2.) was because of the cost benefit-analysis from a small business stand point. Eureka Floor Carpet One was looking for a more energy efficient lighting system and a means to replace their older, magnetic ballast lighting system which had been less cost-effective. <ref name="A">[Mike Jurkovich. Personal Communication. October 20, 2009]</ref> Seventy-four retrofits were performed by the RCEA in April of 2006. A complete list of RCEA retrofits is located in the Summary of Completed Retrofits(Table 3.)


==Data Analysis==
==Data Analysis==
Line 59: Line 59:


===Energy Saved===
===Energy Saved===
After the retrofits, Carpet One experienced a twenty-one percent power reduction during the 2007-2008 year and a three percent energy reduction during the 2008-2009 year. According to Yearly Energy Savings Comparison (Figure 3), Carpet One used less energy during the 2007-2008 year directly following the lighting retrofits. The year after, however, Carpet One experienced an increase in energy use due to the business’s change in habits. This increase in energy use can be attributed to more report lighting use in Carpet One’s warehouse beginning the 2008-2009 year.  
After the retrofits, Eureka Floor Carpet One experienced a twenty-one percent power reduction during the 2007-2008 year and a three percent energy reduction during the 2008-2009 year. According to Yearly Energy Savings Comparison (Figure 3), Eureka Floor Carpet One used less energy during the 2007-2008 year directly following the lighting retrofits. The year after, however, Eureka Floor Carpet One experienced an increase in energy use due to the business’s change in habits. This increase in energy use can be attributed to more report lighting use in Eureka Floor Carpet One’s warehouse beginning the 2008-2009 year.  


===Money Saved===
===Money Saved===
According to Cost Savings Comparison for the 2007-2008 and 2008-2009 years (Figure 4), Carpet One experienced the most cost savings during the 2007-2008 year directly following the retrofits. Even though total energy was reduced during the 2008-2009 year, Eureka Carpet One did not save money as compared to the yearly average savings. These savings are lower than the RCEA projected savings of $2,226.00 dollars per year.  
According to Cost Savings Comparison for the 2007-2008 and 2008-2009 years (Figure 4), Eureka Floor Carpet One experienced the most cost savings during the 2007-2008 year directly following the retrofits. Even though total energy was reduced during the 2008-2009 year, Eureka Floor Carpet One did not save money as compared to the yearly average savings. These savings are lower than the RCEA projected savings of $2,226.00 dollars per year.  


===Simple Payback===
===Simple Payback===
Line 68: Line 68:


===RCEA Projected Savings Versus Actual Savings===
===RCEA Projected Savings Versus Actual Savings===
Eureka Floor Carpet One Yearly Savings and Simple Payback (Table 1) lists the projected and actual savings for the 2007-2008 and 2008-2009 years. All savings projected by the RCEA were overestimated because they were based the conjecture that Eureka Carpet One would continue with the same energy use habits as the year 2006. Eureka Floor Carpet One did not follow energy use habits from 2006 and consequently, the RCEA's projections were lower than actual savings.
Eureka Floor Carpet One Yearly Savings and Simple Payback (Table 1) lists the projected and actual savings for the 2007-2008 and 2008-2009 years. All savings projected by the RCEA were overestimated because they were based the conjecture that Eureka Floor Carpet One would continue with the same energy use habits as the year 2006. Eureka Floor Carpet One did not follow energy use habits from 2006 and consequently, the RCEA's projections were lower than actual savings.


==Effects of Retrofits==
==Effects of Retrofits==
Line 74: Line 74:
=== Customer Satisfaction ===
=== Customer Satisfaction ===


Eureka Floor Carpet One expressed satisfaction with their overall experience with the RCEA staff and contractors. One aspect of the upgrade that Carpet One would have liked to have been more informed about was the presence of more than one electrician working on their retrofits '''(any more detail?).''' Carpet One also believed that analysis took longer to complete than the expected amount of time. <ref name="A">[Mike Jurkovich. Personal Communication. October 20, 2009]</ref>  
Eureka Floor Carpet One expressed satisfaction with their overall experience with the RCEA staff and contractors. One aspect of the upgrade that Eureka Floor Carpet One would have liked to have been more informed about was the presence of more than one electrician working on their retrofits '''(any more detail?).''' Eureka Floor Carpet One also believed that analysis took longer to complete than the expected amount of time. <ref name="A">[Mike Jurkovich. Personal Communication. October 20, 2009]</ref>  
Without the proposal from the RCEA, Carpet One expected to have completed the same lighting upgrade after a period of one and a half years or longer. <ref name="A">[Mike Jurkovich. Personal Communication. October 20, 2009]</ref>  
Without the proposal from the RCEA, Eureka Floor Carpet One expected to have completed the same lighting upgrade after a period of one and a half years or longer. <ref name="A">[Mike Jurkovich. Personal Communication. October 20, 2009]</ref>  


=== Future Upgrades ===
=== Future Upgrades ===

Revision as of 06:27, 12 December 2009

Template:115inprogress

Figure 1. Eureka Floor Carpet One Located in Eureka, California, USA

Template:TOCleft

Introduction

Eureka Floor Carpet One (Figure 1) sells floor coverings and performs installments to homes and commercial businesses across Humboldt County, California. Eureka Floor Carpet One experiences customer visits sporadically throughout the day, sometimes several hours or just a few minutes apart, so lights must remain on constantly during business hours. With the assistance of the Redwood Coast Energy Authority (RCEA), Eureka Floor Carpet One replaced it's old lighting system with new energy efficient lighting. [1]


Before the lighting retrofits, Eureka Floor Carpet One experimented with motion-sensing switches to save energy. Even though Eureka Floor Carpet One was saving Kilowatt-hours, they reported replacing light bulbs more frequently. Before the installment of electronic ballasts during the lighting upgrade, Eureka Floor Carpet One had magnetic ballasts. Each time an older magnetic ballasts stopped working, an electrician would have to be hired to fix it. By participating in the RCEA lighting upgrade, Eureka Floor Carpet One could replace all of the ballasts at once, with the intention of saving time and money on maintenance.[1]

Lighting Retrofits

Figure 2. Lighting Retrofits Performed on Eureka Floor Carpet One by the Redwood Coast Energy Authority

Eureka Floor Carpet One's main purpose for performing the lighting retrofits (Figure 2.) was because of the cost benefit-analysis from a small business stand point. Eureka Floor Carpet One was looking for a more energy efficient lighting system and a means to replace their older, magnetic ballast lighting system which had been less cost-effective. [1] Seventy-four retrofits were performed by the RCEA in April of 2006. A complete list of RCEA retrofits is located in the Summary of Completed Retrofits(Table 3.)

Data Analysis

The RCEA provided data eight months prior to the retrofits. To calculate the yearly average energy use, the sum of the energy used eight months prior to retrofits was divided by eight and multiplied by twelve. This number was subtracted from the sums of the 2007-2008 and 2008-2009 years to find average annual energy savings. This number for average annual energy savings was used in further calculations including energy savings, cost savings, carbon-dioxide savings, and simple payback.

Table 1. Eureka Carpet One Yearly Savings and Simple Payback
Table 1 RCEA Estimate Actual Result (2007-2008) Actual Result (2008-2009)
Energy Savings (Kwh/year) 14,321 1,533 232
Energy Cost Savings (Dollars/month) 185.50 12.50 -1.67
Energy Cost Savings (Dollars/year) 2,226.00 149.96 -20.04
CO2 Savings (Pounds/year) 7,447 1,532.50 231.50
Simple Payback (years) 1.5 41 (no payback)
Figure 3. Yearly Energy Savings Comparison
Figure 4. Cost Savings Comparison for the 2007-2008 and 2008-2009 Years



Energy Saved

After the retrofits, Eureka Floor Carpet One experienced a twenty-one percent power reduction during the 2007-2008 year and a three percent energy reduction during the 2008-2009 year. According to Yearly Energy Savings Comparison (Figure 3), Eureka Floor Carpet One used less energy during the 2007-2008 year directly following the lighting retrofits. The year after, however, Eureka Floor Carpet One experienced an increase in energy use due to the business’s change in habits. This increase in energy use can be attributed to more report lighting use in Eureka Floor Carpet One’s warehouse beginning the 2008-2009 year.

Money Saved

According to Cost Savings Comparison for the 2007-2008 and 2008-2009 years (Figure 4), Eureka Floor Carpet One experienced the most cost savings during the 2007-2008 year directly following the retrofits. Even though total energy was reduced during the 2008-2009 year, Eureka Floor Carpet One did not save money as compared to the yearly average savings. These savings are lower than the RCEA projected savings of $2,226.00 dollars per year.

Simple Payback

Simple payback is the amount of time required to accumulate savings equal to the initial cost of the retrofits. Based on Eureka Floor Carpet One Yearly Savings and Simple Payback (Table 1), initial installation cost of $6,149.99 was divided by the yearly energy savings for the 2007-2008 and 2008-2009 years. If Eureka Floor Carpet One followed energy use for the 2007-2008 year, simple payback would occur in forty-one years as compared to RCEA projected one-and-one-half years. If Eureka Floor Carpet One followed energy use for the 2008-2009 year, simple payback would not occur because no money was saved during the 2008-2009 year.

RCEA Projected Savings Versus Actual Savings

Eureka Floor Carpet One Yearly Savings and Simple Payback (Table 1) lists the projected and actual savings for the 2007-2008 and 2008-2009 years. All savings projected by the RCEA were overestimated because they were based the conjecture that Eureka Floor Carpet One would continue with the same energy use habits as the year 2006. Eureka Floor Carpet One did not follow energy use habits from 2006 and consequently, the RCEA's projections were lower than actual savings.

Effects of Retrofits

Customer Satisfaction

Eureka Floor Carpet One expressed satisfaction with their overall experience with the RCEA staff and contractors. One aspect of the upgrade that Eureka Floor Carpet One would have liked to have been more informed about was the presence of more than one electrician working on their retrofits (any more detail?). Eureka Floor Carpet One also believed that analysis took longer to complete than the expected amount of time. [1] Without the proposal from the RCEA, Eureka Floor Carpet One expected to have completed the same lighting upgrade after a period of one and a half years or longer. [1]

Future Upgrades

Eureka Floor Carpet One has no more lighting available for upgrade, but has expressed interest in both solar electric and solar heating retrofits. [1]


Summary of Completed Retrofits

Table 2. Complete list of lighting retrofits at Eureka Floor Carpet One
Location Pre Retrofit Post Retrofit Installation Cost Annual Projected Savings
Tile Area Four 4' Tubular Fluorescent 12 Lamps (40 watts) Two 4' Tubular Fluorescent 8 Lamps (32 watts) $228.04 $138.88
Restroom Hall One Incadescent A19 Lamp (60 watts) One Compact Fluorescent Lamp (13 watts) $13.07 $16.00
Kitchen/Break Room Two Incandescent A19 Lamps (60 watts) Two Compacts Fluorescent Lamps (13 watts) $2.14 $4.57
Area Rug Room Eight 4' Tubular Fluorescent 12 Lamps (40 watts) Eight 4' Tubular Fluorescent 8 Lamps (32 watts) $456.08 $198.40
Laminate/Tile Area Sixteen 4' Tubular Fluorescent 12 Lamps (40 watts) Sixteen 4' Tubular Fluorescent 8 Lamps (32 watts) $848.00 $238.08
Restroom (M/F) Two Incandescent A19 Lamps (60 watts) Two Compact Fluorescent Lamps (13 watts) $26.14 $4.57
Laminate/Hardwood Area Eleven 4' Tubular Fluorescent 12 Lamps (40 watts) 12 and Five 4' Tubular Fluorescent 12 Lamps (60 watts) Eleven 4' Tubular Fluorescent 8 Lamps (32 watts) and Five 4' Tubular Fluorescent 8 Lamps (32 watts) $939.11 $241.49
Displays Two 4' Tubular Fluorescent 12 Lamps (40 watts) and One 8' Tubular Fluorescent 12 Lamp (60 watts) and Two 4' Tubular Fluorescent 12 Lamps (40 watts) Two 4' Tubular Fluorescent 8 Lamps (32 watts) and One 8' Tubular Fluorescent 8 Lamps (59 watts) and Two 4' Tubular Fluorescent 8 Lamps (33 watts) $347.74 $79.99
Carpet Roll Area/Back Showroom Fifteen 4' Tubular Fluorescent 12 Lamps (40 watts) and Two Metal Halide Lamps (400 watts) One 8' Tubular Fluorescent 12 Lamp (60 watts) Fifteen 4' Tubular Fluorescent 8 Lamps (32 watts) and Two 4' Tubular Fluorescent 8 Lamps (32 watts) and One 8' Tubular Fluorescent 8 Lamp (59 watts) $1218.52 $323.16
Shelly's Office Four 4' Tubular Fluorescent 12 Lamps (40 watts) Four 4' Tubular Fluorescent 8 Lamps (32 watts) $228.04 $193.44
Mail Machine Room One 4' Tubular Fluorescent 12 Lamp (40 watts) One 4' Tubular Fluorescent 8 Lamp (32 watts) $46.96 $1.95
Mike's Office One 4' Fluorescent 12 Lamp (40 watts) One 4' Tubular Fluorescent 8 Lamp (32 watts) $57.01 $35.96
Back Warehouse Exterior Two Halogen lights (300 watts) One Compact Fluorescent Lamp (42 watts) $92.53 $164.66
Back Warehouse One Halogen Light (300 watts) and Six 8' Tubular Fluorescent 12 Lamps (60 watts) and One 4' Tubular Fluorescent 12 Lamp (40 watts) and One 6' Tubular Fluorescent 12 Lamp (55 watts) and One Metal Halide Lamp and One Incandescent A19 Lamp (60 watts) and One 4' Tubular Fluorescent 12 Lamp (40 watts) One Compact Fluorescent Lamp (42 watts) and Six 4' Tubular Fluorescent 8 Lamps (32 watts) and One 4' Tubular Fluorescent 8 Lamp (32 watts) and One 4' Tubular Fluorescent 8 Lamp (32 watts) and One Compact Fluorescent Lamp (13 watts) and One 4' Tubular Fluorescent 8 Lamp (32 watts) $1215.86 $495.53
Main Building Exterior One Mercury Vapor Lamp (175 watts) One Compact Fluorescent Lamp (65 watts) $65.13 $89.35
Lamp and Ballast Disposal N/A 200 4' lamps and recycle non PCB ballast and 8' lamps $241.92 $0.00