This is the Operation and Maintenance (O&M) manual for HEIF CCAT solar hot water system. Please refer to it and keep it up to date with any O&M changes.

Description

The Phoenix Water Heater and Radiant Floors

The HTP Phoenix Gas Fired Water Heater (model PH119S) was installed in 2007 by Stephen Bohner of Alchemy Construction. This water heater is quite advanced, with the following characteristics:

  • Up to 96% efficiency
  • 316L Stainless Steel Tanks are built to withstand high temperatures and have superior corrosion resistance, which extends the life of the unit
  • Internal curponickel/stainless steel heat exchanger that provides exceptional heat transfer capabilities
  • Eliminates the use of anode rods that require costly maintenance and may cause the water to have an unpleasant taste and smell
  • Fully modulating condensing unit with up to a 5-1 turndown ratio. This reduces cycling and conserves energy while meeting desired heating needs
  • The solar heat exchanger is finned, offering more surface area compared to tubes increasing heat exchanger capacity
  • There is a backup heat exchanger that operates when higher recovery rates are needed. With a unique stainless steel and cupronickel design, it is virtually maintenance free, minimizing lime scale build up and eliminating the blockage risk associated with low mass boilers.

The radiant floor system is also hands-off. When the annual or every-other-year inspection of the Phoenix is performed, the radiant system can also be checked for any issues.

The Solar Collectors

The Schuco Premium V Flat Plate Solar Collectors were installed by Ben Scurfield of Scurfield Solar in 2009. These collectors were chosen over more efficient evacuated tubes because they are high quality, low maintenance, and more durable than the evacuated tubes would have been. Some of the product characteristics include:

  • High efficiency with high selectivity absorber coating
  • Low energy loss due to excellent thermal insulation
  • Robust silver anodized aluminum frame for maximum durability
  • Corrosion resistant materials for high reliability and long service life
  • High transparency, low iron glazing
  • Superior flow control over conventional header/riser designs
  • 10 year performance warranty
  • Serpentine piping, with 1 connection on each side for portrait orientation of collector
  • Thermal efficiencies up to 78.4%
  • Thermal output: 2.0 kWth

Figure 4: Oventrop DeltaSol BS differential pump controller and pump. The pump is encased in the black insulation, and the pump controller (bottom center) is no longer used to control the pump.

The Dataloggers

Click here to see data tables recorded by the SunEarth
Click here to see data tables recorded by the CR1000

There are two dataloggers currently recording data from the solar thermal system: the SunEarth Aeca TR0603 mc U and the Campbell Scientific CR1000. It is not clear when both systems were added, but there is data from the CR1000 that dates back to 2010.

Figure 5: The SunEarth datalogger and pump controller.

Figure 6: The Campbell Scientific CR1000 datalogger.

The original purpose of the dataloggers was to record data from the solar thermal system and figure out away to publish that data on CCAT's website as a demonstration of the solar thermal resource and its utilization for domestic hot water and radiant heating at CCAT. However, that goal has not been realized due to the limited institutional memory at CCAT and the complexity of the datalogging and publishing process.

In order to gather information related to these devices, the following sources and individuals were consulted:

  • The original proposal submitted to the Humboldt Energy Independence Fund (HEIF) in the Fall of 2008 to install the solar thermal system and its associated components. The proposal was submitted by Laura Hughes and Jeff Steuben. Peter Alstone was the consulting engineer from the Schatz Energy Research Center.
  • Ben Scurfield of Scurfield Solar also assisted with the installation of the temperature sensors and other devices when the solar thermal system was first installed, and then when it was reinstalled when CCAT was given a new metal roof.
  • Dr. Arne Jacobson from the Environmental Resources Engineering Department and the Schatz Energy Research Center assisted with the HEIF proposal and has also used the solar thermal system as a demonstration in the Solar Thermal course.
  • Roger Tuan has perhaps been the best resource. Roger was a Co-Director at CCAT in 2010. Roger has served in a variety of capacities and has continued to assist with CCAT projects well after his directorship. Roger assisted with connecting to and debugging the CR1000 and was also the source for the data pulled from 2010 and 2011.
  • Chris Stone was not consulted directly, but had a hand in the programming of the CR1000.

Although a system is currently being set up to collect and publish the data from the CCAT photovoltaics system through an ENGR305 student (Jenna Bader), a solution for reliably collecting and publishing the data from the CCAT solar thermal system has not been realized. However, recommendations for next steps are included in the suggestions for the future.

The following information has also been learned about the datalogging devices:

  • The SunEarth is connected to three temperature sensors and one flow meter. The cables can be followed directly from the base of the SunEarth to their respective destinations:
    • The temperature at the outlet of the solar collectors on the roof (recorded in the csv files as T1)
    • The temperature at the outlet of the heat exchanger at the base of the Phoenix hot water heater (recorded in the csv files as T2)
    • The temperature at approximately one third of the way up the Phoenix water heater (recorded in the csv files as T3). It is possible that this temperature represents the temperature at level of the natural gas furnace heat exchanger, potentially serving as a way to separate out the solar thermal resource versus the natural gas contribution toward hot water in the Phoenix. However this is speculation.
    • The flow meter attached to the copper tubing going to the solar collectors on the roof. By inference, it seems that this value is recorded in the csv files as R1, a percentage. Potentially, the percentage represents the time that the pump is turned during the five minute interval over which the SunEarth records data. However, this result is misleading, because it implies that that the pump is operated in an on-off mode with only one speed. However, based on data from the CR1000 (explained below) and visual inspection, it seems that the SunEarth is actually controlling the pump with a differential controller that varies the pump speed according to the differential temperature of the T1 and T2 temperature sensors.
  • The SunEarth records the data on an SD card that can be removed from the slot on the right side of the device. The device records data every five minutes and creates a csv file every day. When the SD card was inspected during this report, the data began in September, 2013.
  • Based on a conversation with Ben Scofield, it seems that the SunEarth pump controller is set to turn the pump on when T1 is fifteen degrees greater than T2 and turn the pump off when T1 is four degrees greater than T2.
  • The CR1000 is a sophisticated (and expensive) device that currently records data related to temperature, solar resource, and flow rate. The leads for the wires connected to the CR1000 disappear into the dropped ceiling of the CCAT basement, so the following is based on inference from the data and from what Roger Tuan remembers from his conversation with the consulting engineer who installed the system:
    • The indoor and outdoor air temperature. There is probably a temperature sensor on the roof to record the outdoor air temperature. However, it is not clear where the indoor air temperature sensor is located. Potentially in the basement in order to calculate the heating load through the radiant heating?
    • The indoor and outdoor H2O temperatures. It is inferred that H2O in this case means the propylene glycol/water mixture in the solar thermal system. Also, since there are no obvious temperature sensors in the basement where the water supply for the domestic hot water originates, it is inferred that these values actually correspond to the temperature of the working fluid at the inlet and outlet of the solar collectors.
    • The solar radiation recorded from a pyranometer located on the roof of CCAT. This value is recorded in Watts per square meter.
    • The flow rate from the flow meter on the solar thermal system. This cable is spliced inside the SunEarth so that the pulses from the flow meter are sent to both the SunEarth and the CR1000. However, while the SunEarth apparently fails to record the flow rate (perhaps because the cables are tied into the wrong port on the SunEarth?), the CR1000 does record the number of pulses during the recording interval. Each pulse corresponds to the passage of one deciliter through the flow meter. This can be observed visually by watching the spinning of the flow indicator on the flow meter on the far left (0.0001m3). Since this value varies over the period which the pump is on, it is clear the SunEarth is acting as a differential controller that controls the pump speed instead of simply an on-off switch. Ben Scurfield indicated that this setting may result in premature wear on the pump, as the varying voltage and current sent to the pump is harder on the pump than simply turning on and off. However, it is not clear whether the premature wear-and-tear is balanced out by the more sophisticated control of the working fluid flow.
  • The CR1000 is designed to run on 12VDC. As a result, there is a charge controller and back up sealed lead acid battery that are connected to the CR1000. These devices are in working order and should not be disturbed.

Figure 7: The flow meter for the Solar Thermal System. It is located in the basement on the piping going to the roof.


Operation

The Phoenix Water Heater and Radiant Floors

The Phoenix is relatively hands-off. However, the most important consideration is keeping the area around the water heater clean and clear. Since it is a natural gas furnace, be sure not to keep anything combustible in the vicinity.

WHAT TO DO IF YOU SMELL GAS
  • Do not try to light any appliance.
  • Do not touch any electrical switch.
  • Do not use any phone in your building.
  • Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
  • If you cannot reach your gas supplier, call the fire department. Installation and service must be provided by a qualified installer, service agency, or the gas supplier.

In addition, in order to ensure the Phoenix has a long life (and doesn't have to be resurrected from the ashes): Do not operate the appliance if its combustion air intake is located in or near one of the areas or in the vicinity of products listed in the following table. These areas will always contain hazardous contaminates that can form strong acids while passing through the burner and vent system. These acids will corrode the appliance’s heat exchanger, burner components and vent system, resulting in flue gas spillage and/or water leakage, possible substantial property damage, severe personal injury, or death. If the appliance combustion air intake is located in any area likely to cause or contain contamination, or if products which would contaminate the air cannot be removed, the intake must be re-piped and terminated to another location.

PRODUCTS TO AVOID

  • Spray cans containing fluorocarbons
  • Permanent wave solutions
  • Chlorinated waxes/cleaners
  • Chlorine-based swimming pool chemicals
  • Calcium chloride used for thawing
  • Sodium chloride used for water softening
  • Refrigerant leaks
  • Paint or varnish removers
  • Hydrochloric or Muriatic acid
  • Cements and glues
  • Antistatic fabric softeners used in clothes dryers
  • Chlorine-type bleaches, laundry detergents, and cleaning solvents

Also, in order to adjust the temperature of stored water, press and hold {S3} for 2 seconds. The first item is: DU: Water Temperature Set Point – factory set at 119°F. Adjust down by pressing {S1} to a temperature as low as 95°F. Adjust up as high as 160°F by pressing the {S2}. Press {S3} again to display DH, the differential which is factory set at 7°F and adjustable down to 1°F by pressing {S1} and up to 18°F by pressing {S2}. Note: Due to the highly advanced control on this water heater, which compensates for varying inlet water temperature, the actual differential temperature may vary slightly from your setting. Press {S3} again to display the factory default temperature measurement in Fahrenheit. Change the default to Celsius by pressing {S1}. When finished, press {S3} one final time to place unit back into operation. The control automatically re-starts if no key is pressed for 2 minutes.

Finally, the radiant floors are controlled by the thermostat in the basement of CCAT. The thermostat is currently programmed to an occupied temperature and an unoccupied temperature. These temperatures, as well as the occupied and unoccupied settings, can be modified by reprogramming the thermostat.

Figure 2: Thermostat for radiant floors in the basement of CCAT.

Figure 3: Taco X - Pump Block XPB 1 -- ZCV Zone Valve Control .

The Solar Collectors

The system is designed to require no operational attention and very little maintenance attention.

The Dataloggers

Both datalogging devices are designed to run autonomously with little or no operational attention. A person can cycle through the T1 and T2 temperatures on the SunEarth display to confirm that it is on and working. Also, since the SunEarth serves as the pump controller, it is important to make sure that the pump stays plugged into the SunEarth and not into the wall.

Once a reliable procedure is established for collecting and storing the data from both devices, there may be a need to regularly remove the SD card and record the data in a reliable location.

Figure 8: Pump power cord plugging into the base of the SunEarth datalogger and differential pump controller.


Maintenance

Maintenance Schedule

Periodically
  • Check area around the appliance.
  • Check the temperature/pressure gauge
Monthly
  • Check exhaust vent and intake pipe bracing. Ensure bracing is undamaged and in good condition.
  • Check the pressure relief valve.
  • Check the condensate drain system.
  • Check the pressure gauge for the closed-loop solar thermal system.
Every Six Months
  • Check appliance piping and gas supply piping for corrosion or signs of potential leakage.
Every Year
  • Check the pH of the propylene glycol/water mixture on the solar collector loop.
  • Have Plant Ops clean off the solar collectors and check the piping and fixtures on the roof.
Every Three Years
  • Boiler cleaning and overall assessment by a qualified technician. Alchemy Construction estimates that this maintenance will take approximately two hours at $110/hour, totaling $220
  • Have a qualified professional check the pressure of the expansion tanks. The expansion tanks have to be separated from the system pressure in order to be measured.
Every Ten Years
  • Have a qualified professional change the propylene glycol/water mixture and replace the expansion tanks.

Maintenance Instructions

How to maintain the solar hot water system

Troubleshooting

The Phoenix Water Heater
Problem Suggestion
HEATER ERROR
  • When an error condition occurs the controller will display an error code on the display module.
  • These error codes and several suggested corrective actions are included in Table 14 of the installation manual.
  • In the case of E00, E13, and E14 this error, if uncorrected, will go into a fault condition (lockout).
LOCKOUT
  • When a fault condition occurs the controller will illuminate the red “fault” indication light and display a fault code in the format (Example: F00) on the display module.
  • Note the fault code and refer to Table 15 for an explanation of the fault code along with several suggestions for corrective actions.
  • Press the reset key to clear the fault and resume operation. Be sure to observe the operation of the unit to prevent a recurrence of the fault.
The Solar Collectors

The propylene glycol mixture prevents the system from freezing. In addition, the system was designed with steam-back protection to protect it from overheating. If the pump were to break down, the system is designed so that the amount of propylene glycol that would vaporize would fill the expansion tank without causing damage to the system. If you have any concerns that the pump is not working, or if you think there is a leak, call a professional immediately to inspect the system. Do not attempt to fix it yourself, as the contents may be highly pressurized and very hot!

Do not be alarmed by the fact that the Oventrop DeltaSol BS controller for the pump is not connected to anything. The Oventrop controller was replaced by the SunEarth controller and datalogger (see below), but it was left in place in order to preserve aesthetics and because it would otherwise leave a large hole in the insulation.

The Dataloggers

If it seems that the SunEarth is not on or that the pump is not functioning, make sure that the SunEarth power cord is still plugged into the wall. Otherwise, consult a professional like Ben Scurfield as soon as possible.

Suggestions for future changes

The Phoenix Water Heater

Overall, neither the Phoenix Water Heater nor the radiant floors should require much attention. The most important thing is to keep that basement room clear of hazardous materials and clean. It will also be important to establish a regular maintenance schedule with Alchemy Construction with a reliable place to record when maintenance occurred.

The Solar Collectors

The solar thermal collectors were designed to not require much attention. Figure out a reliable way to keep track of the long-term maintenance tasks.

The Dataloggers

In consultation with Roger Tuan, the following represent our recommendations for next steps:

  • Ideally, all the data would be recorded by one device so that data does not have to be regularly collected from two different devices (this is particularly true for the SunEarth that generates a csv file for each day, whereas the CR1000 data is already compiled in one file). This can be achieved by splicing the connections currently going into the SunEarth and taking them into the CR1000 (in the same way that the flow meter is currently spliced in the SunEarth).
  • Ideally, there would also be a device like a Raspberry Pi that would regularly record the data from the dataloggers and publish it on the internet. If the project currently underway with the PV system is successful, it is possible that Linux based software can be installed on the Raspberry Pi to automatically record and publish the data from the CR1000 in addition to the data being recorded and published from the Aurora inverter.

Unfortunately, the CR1000 has not been recording data for the last four years. Apparently, the data logging program was loaded on the CR1000 but not active. It is imperative that backup copies of this program are made because installing a new program would require knowing all the specifications of the sensors which are currently scattered through CCAT or on CCAT's roof. However, as of the writing of this report, both the SunEarth and the CR1000 are recording data from all the sensors to which they are connected.